Low frequency Online UPS 100-200K
|
MODEL |
PTT-100K |
PTT-120K |
PTT-160K |
PTT-200K |
RATED CAPACITY |
100KVA/80KW |
120KVA/96KW |
160KVA/128KW |
200KVA/160KW |
Input voltage |
380-400-415V AC Three phase |
Voltage Tolerance |
400V ¡À 20% |
Current Tolerance |
< 3% in the 12MP HC version |
Input Frequency |
45~65Hz |
Freqeucny Tolerance |
¡À 2% |
Input Power factor |
> 0.95 in the 12MP HC version |
Soft Start |
0~100% in 30 " (Optional) |
Standard Function |
Feedback protection, independent bypass |
Output voltage |
380-400-415V AC 3+N |
Static stability |
¡À 1% |
Dynamic stability |
¡À 5% within 10ms |
Voltage distortion |
Linear load <1%, distorting load <3% |
Output Frequency |
50Hz or 60Hz optional ¡À 0.5% |
Output power factor |
0.8 |
Output wave form |
True sine wave |
Overload capacity |
>110% 60min. >125% 10min. >150% 1min. |
Load crest ratio |
3 : 1 max |
Battery type |
Maintenance free sealed lead acid |
Battery voltage |
432V DC |
480V DC |
480V DC |
480V DC |
Current exchange |
< 1% |
Temperature Compensation |
oC x -5V |
Rush charge current |
0.2 x C10 |
Long-distance signal |
Dry connected |
Long-distance order |
EPO, Bypass |
Communication |
double RS232 + remote contacts + 2 communication interface slots |
Efficiency |
Up to 94% |
Dimension |
1900 x 800 x 800 mm |
UPS Weight |
640Kg |
650Kg |
770Kg |
810Kg |
Noise |
63~68DBA, < 1m |
Temperature |
0~40oC |
Humidity |
0~95% non-condensing |
Altitude |
<1500m |
Storage |
©¤ 25~55oC |
IP Class |
IP20 |
STANDARD |
Directives EC 73/23 - 93/68 - 2004/108; Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3 |
|